Troubleshooting Lippert Ground Control 3.0 Controller Going Blank Mid Level and No Longer Working  

Question:

My six point self leveling system quit halfway through leveling the screen is entirely blank there are no fuses in the module or controller

0

Expert Reply:

On your Lipper Ground Control 3.0 6-Point Leveling System # LC675817 the only thing that would cause the system to shut off midway through leveling and have a blank screen on the controller would be the main circuit breaker to the battery tripping.

There should be a 50 amp circuit breaker running from the battery to the controller, I recommend tracing the power wire from the controller back to the battery and checking the circuit breaker. If a none auto resetting breaker was installed you will have to manually reset it.

If you reset the breaker and the system does not come back on you will need to use a circuit tester like # 40376 to test both sides of the circuit breaker to see if there is power making its way through it. If there is not then the circuit breaker is bad and you will need to replace it with the # PK54250.

I included videos of the products mentioned for you to take a look at.