Does The AC Distribution Panel Of The PD4135K Power Center Need To Be Ground To The RV Chassis  

Question:

Does the AC ground bus bar need to be grounded to the chassis or just the white DC side?

0

Expert Reply:

The AC distribution panel of the Progressive Dynamics 4100 Series RV Converter w/ Charge Wizard and AC/DC Distribution Panel # PD4135K is being grounded at the shore power connection point so you wouldn't need to ground it to the frame of the RV. The DC side would need to be grounded to the frame of the RV.