Firman Parallel Power Kit Not Reading Correct Voltage At Plugs, And Plugs Don't Work
Question:
I bought Item # 333-0007 and when connected and both generators are running it works great. My question is, why are all the plugs on the generators when tested are only showing 55-60 volts and cant be used? Thanks
asked by: Glenn
Expert Reply:
I spoke with Firman, the manufacturer of the Parallel Power Kit for etrailer Inverter Generators # 333-0007, and they believe that you are most likely only testing one of the leads and the ground or the neutral.
What you'll need to do is, test both of the hot leads together and they should read 120v.
I have attached a picture of the schematic and which prongs to test on the 50 amp.
Product Page this Question was Asked From
Parallel Power Kit for etrailer Inverter Generators - 120 Volt - 50 Amp
- Accessories and Parts
- Generators
- Parallel Kit
- etrailer
more information >
Featured Help Information
Instructions
Miscellaneous Media
Continue Researching
- Q&A: What is Differene Between Dometic Full Timer RV Toilets 320 and 510
- Q&A: Distance from Mounting Bolt Center of Dometic 320 Full Timer RV Toilet DOM87FR to Rear of Toilet
- Q&A: How Many Adjustable Mount Kits Are Needed for a 4 Panel Solar Charging System
- Q&A: Seat Size Of The Dometic Full-Timer RV Toilet
- Q&A: Can A Dometic 320 Series RV Toilet Replace A Dometic 300 Series RV Toilet
- Q&A: Can I Add the Hand Sprayer to a Dometic 320 Series Toilet After Purchase
- Q&A: Does Dometic 320 Full-Timer RV Toilet Come with Handheld Sprayer
- Article: Best RV Roof Vents
- Article: Calculating Portable Generator Power Needs
- Article: 4 Steps to Choosing Your 5th Wheel Pin Box
- Article: Best 2020 Heavy Duty Trucks for Towing a 5th Wheel
- Article: RV Cell Boosters, How Do They Work?
- Article: Which RV Propane Tank Size Do I Need?
- Article: How Much Solar Power Do I Need For My RV?